CCMHQ - P/N N1105RN148 FLOODED LEAD-CALCIUM BATTERY
- MSDS: CCMHQ
- Manufacturer: C AND D POWER SYSTEMS AN ALLIED CO
- Product Name: P/N N1105RN148 FLOODED LEAD-CALCIUM BATTERY
- National Stock Number: 6140-00-202-2978
Product Identification
Product ID:P/N N1105RN148 FLOODED LEAD-CALCIUM BATTERY
MSDS Date:07/01/1994
FSC:6140
NIIN:00-202-2978
MSDS Number: CCMHQ
Responsible Party
PLYMOUTH MEETING, PA 19462
US
Emergency Phone: 215-828-9000
Info Phone: 215-828-9000
Preparer: P.J. REICH
Cage: 1K126
Contractor
Telephone: 215-619-2700
Cage: 1K126
Ingredients
LEAD (SARA 313) (CERCLA)
CAS: 7439-92-1
RTECS: OF7525000
Fraction By Weight: 62-65%
OSHA PEL SEE 1910.1025
ACGIH TLV: 0.05MG/M3, A3; 9596
EPA Report Quantity: 1 LB
DOT Report Quantity: 1 LB
SULFURIC ACID (SARA 302/313) (CERCLA)
CAS: 7664-93-9
RTECS: WS5600000
Fraction By Weight: 6-8%
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3/3 STEL; 9596
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
WATER
CAS: 7732-18-5
RTECS: ZC0110000
Fraction By Weight: 12-15%
CALCIUM, METAL
CAS: 7440-70-2
RTECS: EV8040000
Fraction By Weight: 1%
INERT INGREDIENTS
Fraction By Weight: 10-18%
Hazards
LD50 LC50 Mixture:ORAL LD50 (RAT) IS 2140 MG/KG (ACID)
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:NO IARC:YES OSHA:NO
Health Hazards Acute and Chronic:ACUTE: TISSUE DESTRUCTION ON CONTACT
WITH ACID ELECTROLYTE; MAY CAUSE 2D/3D DEGREE BURNS. INGESTION WILL
CAUSE BURNS ON CONTACT; FATAL IF SWALLOWED. CHRONIC:
PROLONGED/REPEATED INHALATION OF ACID MIST S MAY CAUSE UPPER
RESPIRATORY IRRITATION.
Explanation of Carcinogenicity:INORGANIC ACID MISTS CONTAINING SULFURIC
ACID ARE LISTED AS A CATAGORY 1 CARCINOGEN BY IARC. (BATTERY
CONTAINS LIQUID).
Effects of Overexposure:EYES-IRRITATION, BURNS. SKIN-IRRITATION, BURNS.
INGESTED-BURNS. INHALED-RESPIRATORY IRRITATION.
Medical Cond Aggravated by Exposure:OVEREXPOSURE TO ACID MAY AGGRAVATE
RESPIRATORY DISORDERS.
First Aid
First Aid:IN ALL CASES GET MEDICAL ATTENTION. EYES-FLUSH WITH WATER FOR
15 MINUTES. SKIN-REMOVE CONTAMINATED CLOTHES. WASH WITH MILD SOAP &
WATER. INHALED-REMOVE TO FRESH AIR. ADMINISTER OXYGEN OR ARTIFICIAL
RE SPIRATION AS NEEDED. INGESTED-DO NOT INDUCE VOMITING! IF
CONSCIOUS, DRINK LOTS OF WATER OR MILK. OBTAIN IMMEDIATE MEDICAL
ATTENTION.
Fire Fighting
Extinguishing Media:CARBON DIOXIDE, DRY CHEMICAL, HALON.
Fire Fighting Procedures:VENTIALTE AREA. WEAR SELF-CONTAINED BREATHING
APPARATUS AND ACID PROTECTIVE CLOTHING.
Unusual Fire/Explosion Hazard:HYDROGEN GAS MAY BE PRESENT. HYDROGEN &
SULFURIC ACID MIST ARE GENERATED UPON OVERCHARGE OR IN FIRE.
VENTILATE AREA THOROUGHLY.
Accidental Release
Spill Release Procedures:NEUTRALIZE ANY SPILLED ELECTROLYTE OR EXPOSED
BATTERY PARTS WITH SODA ASH OR SODIUM BICARBONATE UNTIL FIZZING
STOPS. PH SHOULD BETWEEN 6 & 9. KEEP UNTRAINED PERSONS AWAY. PLACE
BROKEN BATTERY IN PLAST IC BAG. PROVIDE ADEQUATE VENTILATION.
Neutralizing Agent:SODA ASH OR SODIUM BICARBONATE.
Handling
Handling and Storage Precautions:STORE IN A COOL, DRY PLACE AWAY FROM
COMBUSTIBLES. DO NOT STORE IN SEALED, UNVENTILATED AREAS.
Other Precautions:DO NOT USE ORGANIC SOLVENTS OR OTHER THAN RECOMMENDED
CHEMICAL CLEANERS ON THE BATTERIES. DO NOT WEAR CONDUCTIVE METAL
JEWLRY WHEN WORKING WITH BATTERIES. USE NON-CONDUCTIVE TOLLS ONLY.
DISCHARGE STAT IC ELECTRICITY BEFORE HANDLING BATTERY.
Exposure Controls
Respiratory Protection:IF ENGINEERING CONTROLS FAIL OR NON-ROUTINE USE
OR AN EMERGENCY OCCURS; WEAR AN MSHA/NIOSH APPROVED RESPIRATOR WITH
ACID MIST CARTRIDGE OR AN AIR-SUPPLIED RESPIRATOR OR SCBA, AS
REQUIRED. USE IAW 29 C FR 1910.134.
Ventilation:USE ADEQUATE GENERAL ROOM VENTILATION (2-3 ROOM CHANGES OF
AIR PER HOUR) TO MAINTAIN EXPOSURE BELOW TLV(S).
Protective Gloves:RUBBER OR NEOPRENE.
Eye Protection:SAFETY GLASSES/CHEMICAL SPLASH GOGGLES.
Other Protective Equipment:EYE WASH STATION & SAFETY SHOWER. ACID
RESISTANT APRON OR CLOTHES.
Work Hygienic Practices:WASH HANDS AFTER HANDLING AND BEFORE EATING,
DRINKING, OR SMOKING. LAUNDER CONTAMINATED CLOTHES BEFORE REUSE.
Supplemental Safety and Health
PHYSICAL & HEALTH DATA BASED ON ACID ELECTROLYTE.
Chemical Properties
HCC:C1
Boiling Pt:B.P. Text:235F,113C
Vapor Pres:1
Vapor Density:>1
Spec Gravity:1.215
Evaporation Rate & Reference:<1 (WATER=1)
Solubility in Water:COMPLETE (ACID)
Appearance and Odor:LEAD-ACID BATTERY; 2 TERMINAL; 18.5 INCHES X 30.375
INCHES X 31 INCHES.
Stability
Stability Indicator/Materials to Avoid:YES
CONDUCTIVE METALS, ORGANIC SOLVENTS, SPARKS OR OPEN FLAME.
Stability Condition to Avoid:NONE SPECIFIED BY MANUFACTURER.
Hazardous Decomposition Products:HYDROGEN GAS MAY BE GENERATED DURING
OVER CHARGE, IN FIRE OR EXPOSURE TO HIGH TEMPERATURES. FIRE ALSO:
CO, CO2, SULFIDE.
Conditions to Avoid Polymerization:WILL NOT OCCUR.
Disposal
Waste Disposal Methods:THIS BATTERY IS RECYCLABLE. IT IS ILLEGAL TO
DISPOSA OF LEAD-ACID BATTERIES BY ANY MEANS OTHER THAN RECYCLING.
HAZWASTE CODES: D002, D008. C & D MAINTAINS NATION-WIDE BATTERY
COLLECTION & RECYCLING PR OGRAM; CONTACT C & D FOR MORE
INFORMATION.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.